HomeMy WebLinkAbout050920_6845 Shingle Creek Pkwy Bt50-h
al
i
To: Mr. Mark Hartfiel At: City of Brooklyn Center
From: Steve Cannon At: FM Global
Subject: Water test results Date: September 21, 2005
This memo is intended to provide you with the results of the recent hydrant test
performed on Tuesday, September 20th at the Martin J. Ruter Garage(6845 Shingle
Creek Parkway). The test was conducted with a member of your staff.
The hydrant to the west of the facility was gauged and the next hydrant to the east(north
of plant)was flowed. Water was flowed out of two, 2 %4 in. FM Nozzles (coefficient=
0.88). The test was conducted at 11:30 am. The results are:
Static Pressure: 65 psi
Residual Pressure: 60 psi
Flow: 1785 gpm (pitot pressures of 45 psi out of each nozzle)
If you have any questions about these results,please feel free to contact me. Your
assistance with this test was very much appreciated and I look forward to working with
you again in the future.
Best Regards,
Steve Cannon
Consultant Engineer II
FM Global
St. Louis Operations
Minneapolis Branch Office
Phone: 612-331-1023
Cell: 612-202-3502
Office: 209 5h St. SE Apt. 205
Minneapolis, MN 55414
Email: steven.cannon@fmglobal.com