HomeMy WebLinkAbout090803_1501 Freeway Blvd Skyline Fire Protection, Inc. - Commercial/Industrial Fire Sprinkler Contracting WATERFLOW TEST RESULTS (HYRANT# STATIC PSI RESIDUAL PSI ELEVATION HYDRANT BUTT ORFICE SIZE HYDRANT CO-E PITOT PSI FLOW TABLE Ql ACT'L FLOW Q2 I A 67 65 94695 B 849.15 4.5" $3 Rc 9(� 39 3320 2480 SITE SKETCH TEST SITE INFORMATION HYD A-�J-j L PROPERTY NAME: GSA PROPOSED BUILDINGS FREEWAY BOULEVARD _ T_ 8"WATERMAIN ADDRESS: FREEWAY BLVD&HUMBOLT AVE. HYD B BROOKLYN CENTER,MN 55430 jOFFIC! OSED ¢ ZZ j I F I TEST DATE: 8.3,2009 4 o W TEST TIME: 1:10 PM 3 Q 5w oa a TESTED BY: BOB KOKALES, SKYLINE FIRE PROT. OBSERVED BY: JEFF WITH BROOKLYN CENTER OUTILITIES DEPARTMENT N WATER FLOW CURVE 120- 1 I I I I 1 110 100 90 I I I I I L I I I 80 70 I Cn 60 I 50 I I I I I I 40 I I I I I I 30 20 I I I I I I I I 10 II 1 IlT1.8S 0 8C0 1200 1600 2000 2.00 2800 I '13200 3600 LILLLLWIJLLIJLL L4000 WATER FLOW(GPM) 10900 73rd Avenue North, Suite#108,Maple Grove,MN 55369: Tel: (763)425-4441 -Fax: (763)425-7755